BEx1 module can be installed in Zone 1/21 with certified Ex e enclosure and connects sensors and actuators from Zone 0/20.
BEx2 module can be installed in Zone 2/22, in a suita-ble housing according EN 60079-7:2018 with a protec-tion degree of at least IP 54 and connects sensors and actuators from Zone 0/20.
▪ Full potting → etreme robust
▪ IO variations
• 16xDI Namur / 16xDO
• 32x DI Namur
• 8xDI Namur / 8xDO / 8xAI / 8xAO
• 8xDI Namur / 16xDO / 8xAI
• 8xDI Namur / 8xDO / 8x Switch Mode
▪ None configuration on module required
▪ Separate power supply for sensor and actuator
▪ Comprehensive diagnostics for each channel
• open load detection
• prefault detection
• short circuit detection
▪ Galvanic separation between channel and system
▪ Internal temperature monitoring
▪ Operating hour counter
BEx1 Explosion protection
EPS 19 ATEX 1 219 X
II 2(1) G Ex eb mb [ia Ga] IIC T4 Gb
II (1) D [Ex ia Da] IIIC
IECEx EPS 19.0093X
Ex eb mb [ia Ga] IIC T4 Gb
[Ex ia Da] IIIC
BEx2 Explosion protection
EPS 19 ATEX 1 248 X
II 3(1) G Ex ec mc [ia Ga] IIC T4 Gc
II (1) D [Ex ia Da] IIIC
IECEx EPS 19. 0111X
Ex ec mc [ia Ga] IIC T4 Gc
[Ex ia Da] IIIC
Operating voltage UA/ US DC 18 ... 30V
Power supply moduleand sensors IS DC 450 mA
Power supply actuators IA DC 300 mA
Power loss max. 15W
Reverse polarity protection Yes
Range of the service temperature after installation inside
Additional housing -40°C ... +70°C
Storage temperature -40°C ... +80°C
Degree of protection (EN 60529) IP 20
Fieldbus data
Addressing Profinet via DCP
Addressing Modbus TCP / IP DHCP or fix
Transfer rate 10/100 Mbps
Delay at signal change <10ms
• 16xDI Namur / 16xDO
• 32x DI Namur
• 8xDI Namur / 8xDO / 8xAI / 8xAO
• 8xDI Namur / 16xDO / 8xAI
• 8xDI Namur / 8xDO / 8xSwitch Mode
Dimensions (LxWxH) 214 x 132 x 65 mm
Installation position any position
Weight approx. 2700 g
Housing material Aluminium (electroplated)